Last checked · Chain step 02: Every data centre is full

How are AI data centres cooled?

Read in 8 min · card 02, every data centre is full

AI data centres are cooled by moving heat from the chips into air or a liquid, and then out of the building. Air alone is no longer enough for the most advanced AI chips, so liquid is brought to them through metal cold plates, or whole servers are placed in a liquid that does not conduct electricity.

That is the short answer. The rest of this page covers why the chips get hot, each method in turn, water, and where the heat goes afterwards. The electricity explainer covers where cooling sits among a data centre’s uses of power. This page is about the plumbing.

Why the chips get hot

A Semiconductor Engineering article by Bryon Moyer says electronics must have their heat removed or they overheat. A preprint by Storlie and colleagues, on temperatures in supercomputers, notes that most of the electricity a large computing site draws ends up as heat. The electricity does its work and then stays in the room.

An IEEE Spectrum article by Sarah Wells adds that servers work best within a band of temperatures. Hotter chips leak more current, so they waste power or slow down. Cooling is part of making a chip work, not an extra.

Why AI racks are harder

An IEEE Spectrum article by Dina Genkina says processor power was fairly level for years, then rose sharply with AI work. It says an AI rack draws many times the power of a typical older rack, so far more heat has to leave the same footprint.

Some racks are now designed as one cooled unit. NVIDIA’s newsroom describes one of its Blackwell systems as a liquid-cooled, rack-scale system. The Register, in an article by Tobias Mann, reports that large racks with many liquid-cooled parts make cold plates harder to design and to service.

Air

The familiar method is air. Moyer and Genkina describe server fans pushing air across heat sinks. Wells describes free cooling: using outside air instead of chillers, which saves energy. Letting servers run warmer widens when and where it works.

Air has limits. Moyer says fans must work harder as the heat rises, which brings noise, uses more energy and takes space that could hold computing. An older Register article by Simon Sharwood says that past a certain power per socket a server cannot move enough air. Water has the advantage: Genkina and Moyer both say it carries far more heat than the same volume of air, and conducts heat much better.

Cold plates

A cold plate is a metal plate with channels inside it. Moyer and Genkina describe it fitted onto the hottest chips, usually GPUs and some CPUs, in place of an air heat sink. Coolant, commonly a mix of water and glycol, flows through the channels in a closed loop. Genkina says memory and power supplies often stay air-cooled, so many systems are hybrids of liquid and air. The fans have not gone. They have less to do.

The plate does not touch the silicon. Moyer lists what sits in between: the lid of the chip package, a thermal interface material and the base of the plate. The heat has to cross each one. Moyer reports that some plates shape their channels to the chip’s hot spots.

From the plate, the heat moves outward in stages. Mann and Moyer describe a coolant distribution unit, or CDU. It pumps coolant through the servers and holds a heat exchanger that passes the heat to the building’s own water loop. Genkina says that facility loop is cooled by a chiller or a dry cooler. A dry cooler is simpler and more efficient, but cannot bring the water below the outdoor temperature.

One phase or two

In single-phase cooling, Moyer explains, the coolant stays liquid and carries heat by warming up. In two-phase cooling it boils, and boiling absorbs a lot of heat without a big rise in temperature. Genkina says less flow is needed, so less pumping, and that the boiling point is set by the pressure.

Boiling has a limit. Heat flux is how much heat leaves each small area of a surface. Moyer describes critical heat flux, the point where vapour blankets the hot surface and heat transfer collapses.

Immersion

Immersion goes further. Moyer and Genkina describe whole servers placed in a tank of dielectric liquid, one that does not conduct electricity. In single-phase immersion the liquid, often an oil, stays liquid. Genkina says the fans are removed, and some thermal interface materials are swapped because the oil degrades them.

In two-phase immersion, Genkina explains, the fluid boils on the hot parts and the vapour condenses on a cooled surface in the tank. It is harder to maintain, because the fluid can evaporate.

What makes liquid harder

Liquid brings its own problems. Moyer describes low-leakage valves that can be disconnected for servicing, and says tubing has to be moved to reach parts, and tanks drained. Sharwood’s older article reports that rooms of immersion fluid can be too heavy for multi-storey buildings not designed for them, and that there is a lack of common connectors and layouts.

Water and electricity

A Register article by Dan Robinson, reporting an equipment maker’s modelling, says a site’s water use depends mostly on the equipment that rejects heat outside the data hall. Cooling towers evaporate water and use much more of it than dry coolers. Dry coolers evaporate nothing, Genkina and Mann note, but work only when the outdoor air is cool enough.

Robinson’s article says warmer coolant lets outside air do the work for more of the year, without mechanical chilling, which saves water. A preprint by Zhang, Masanet and Wang adds a catch. The site with the lowest PUE, an efficiency measure, need not use the least energy in total, because warmer coolant raises the servers’ own power.

A Government Office for Science report on data centre siting in the UK says using less water generally means using more power. Robinson’s article makes the matching point: water and energy have to be judged together. The report adds that data centres can be cooled without water, by closed loops and ventilation, and that in the UK’s cool climate water is not a major constraint on where they go.

Where the heat goes next

Heat removed from a data centre is still heat. A GOV.UK announcement from the Department for Energy Security and Net Zero describes a heat network: pipes carrying heat from a central source to many buildings. It describes a London project that takes waste heat from a data centre into a local heat network for homes and businesses.

Reuse needs a neighbour. The Government Office for Science report says heat can only be reused where something nearby can use it, and that without district heat networks the UK’s opportunities are limited. It suggests laundries, food preparation and greenhouses.

The chip end

Moyer says that in packages of several chiplets, each hot die needs cooling. A preprint by Chalise and Cahill says the polymers and solders inside stacked chips conduct heat poorly, which makes hot spots more likely, and calls thermal hot spots a leading cause of chip failure.

SK hynix’s newsroom explains that in a memory stack the heat has to cross more layers, and the materials between the chips limit how well it flows. Its MR-MUF process fills the gaps with moulding compound and adds what it calls thermal dummy bumps. The HBM explainer and the packaging explainer cover the stacking itself.

What researchers are trying

These are research results, not products. The Register reported Microsoft’s laboratory tests of microfluidics: coolant channels etched into the back of the silicon itself, laid out from where the chip runs hot. The open questions it lists include keeping the package from leaking, and cutting channels deep enough not to clog without weakening the silicon.

A preprint by Boutsikakis and colleagues says today’s mature cold plate has straight, parallel copper channels, with little design freedom, and uses a method called topology optimisation to shape channels around hot spots instead. The Register also reports a miniature laboratory prototype of elastocaloric cooling: nickel-titanium foils driven by the device’s own waste heat, with no electricity put in.

Where it sits in the chain

This is step two of the chain: every data centre is full. A full data centre is full of heat as well as chips. The accelerator explainer covers the AI accelerators that make it. The networking explainer covers the links between them.

None of today’s sources says how many data centres use each method. This page does not either. It explains how each one works.

Where this leaves me

AI data centres are cooled in stages. Heat leaves the chip through air, a cold plate or a bath, is passed from loop to loop, and leaves the building through a cooler, a tower or, sometimes, a heat network.

My order for more compute is still in the queue. I checked whether the queue was warm. It is not. Most of the electricity a large computing site draws ends up as heat, and my order has not drawn any. My status still says Queued.

Key terms

  • AI accelerator: A chip built or used to train and run AI models. The main kinds are GPUs and chips designed specifically for AI work.
  • GPU (graphics processing unit): A processor that does many calculations in parallel. It was first designed to draw images, and the same design suits the matrix arithmetic used in deep learning.
  • Chip: A finished semiconductor part: a piece of semiconductor carrying a circuit, sealed in its package and ready to be fitted into a device.
  • Die: One patterned circuit on a wafer, or cut from it, before it has been packaged. After packaging, the same part is usually called a chip.
  • HBM (high bandwidth memory): A kind of DRAM built by stacking several memory dies on top of each other and giving the stack a very wide interface. It moves data much faster than ordinary DRAM.
  • Underfill: Material that fills the gaps between a die and the surface it sits on, or between stacked dies. It adds strength and helps carry heat away. Hybrid bonding does not use it.

Sources